Siemens | F002 Fault

1. Overview Fault Code: F002 Associated Systems: Siemens SINAMICS (G120, S120, G130, G150) and legacy MASTERDRIVES (6SE70). Fault Class: Overvoltage / DC link overvoltage. Immediate Reaction: Drive trips (OFF2), motor coasts to a stop.

| Drive Supply Voltage | DC Link Trip Level (approx.) | |----------------------|------------------------------| | 230V (1-phase) | 410 – 420 V DC | | 400V (3-phase) | 820 – 850 V DC | | 690V (3-phase) | 1100 – 1150 V DC | siemens f002 fault

The F002 fault indicates that the voltage in the DC link of the drive has exceeded the permissible maximum threshold. This is a critical protective function, as excessive DC link voltage can destroy drive components, particularly the DC link capacitors and the braking chopper. The trip level depends on the supply voltage rating: Immediate Reaction: Drive trips (OFF2), motor coasts to

Always verify the braking chopper and resistor health before replacing the drive – a new drive will trip F002 just as fast if the external braking circuit is faulty. For specific parameter numbers, always refer to the drive’s current parameter manual, as Siemens occasionally updates parameter lists between firmware versions. The trip level depends on the supply voltage